Key Features
- Primary and Secondary Inputs for Power Redundancy
- Provides remote power monitoring and enables redundant power for network devices with non-redundant power supply configurations
- Dual 3.6 m input cords with IEC-320 C14 plugs connect to separate primary and secondary single-phase power sources
- 8 switched and 2 unswitched C13 outlets
- Automatic Transfer Switching
- Dynamic solid-state (TRIAC) automatic transfer switching
- Switches to secondary power source if primary source fails or becomes unstable
- 2-5 ms transfer time ensures uninterrupted operation of connected equipment
- Built-in processor monitors both sources and prevents switching if secondary source is unavailable or of lower quality than primary source
- Digital Load Meter
EATON TRIPP LITE SERIES 2.4KW SINGLE-PHASE SWITCHED AUTOMATIC TRANSFER SWITCH PD
PDUMH15HVATNET
SKU 4711519
UPC 037332197504
Regular price saves you $693.66 against MSRP.
Contact us to check availability
Product Overview
EATON TRIPP LITE SERIES 2.4KW SINGLE-PHASE SWITCHED AUTOMATIC TRANSFER SWITCH PD
- Tripp Lite series (PDUMH15HVATNET) PDU
- Eaton Tripp Lite Series 2.4kW Single-Phase Switched Automatic Transfer Switch PDU, Two 200-240V C14 Inlets, 10 C13 Outputs, 1U, TAA - IEC 60320 C14 - 10 x IEC 60320 C13 - 200 V AC, 208 V AC, 220 V AC, 230 V AC, 240 V AC - 2.40 kVA - Network (RJ-45) - 1U/2U - Horizontal Rackmount
- Eaton Tripp Lite Series 2.4kW Single-Phase Switched Automatic Transfer Switch PDU, Two 200-240V C14 Inlets, 10 C13 Outputs, 1U, TAA
- IEC 60320 C14 - 10 x IEC 60320 C13 - 200 V AC, 208 V AC, 220 V AC, 230 V AC, 240 V AC - 2.40 kVA - Network (RJ-45) - 1U/2U - Horizontal Rackmount
Technical Specifications
| Product Type | PDU |
| Input Voltage | 230 V AC |
| Manufacturer Part Number | PDUMH15HVATNET |
| Packaged Quantity | 1 |
| Limited Warranty | 2 Year |
| Output Voltage | 200 V AC |
| Output Voltage | 208 V AC |
| Output Voltage | 220 V AC |
| Output Voltage | 230 V AC |
| Output Voltage | 240 V AC |
| Weight (Approximate) | 10.41 lb |
| Input Current | 10 A |
| Manufacturer | Eaton Corporation |
| Product Model | PDUMH15HVATNET |
| Product Name | PDUMH15HVATNET 10-Outlet PDU |
| Mount Type | Rack-mountable |
| Protection Type | Overload Protection |
| Rack Height | 1U/2U |
| Brand Name | Tripp Lite series |
| Plug/Connector Type | IEC 60320 C14 |
| Input Voltage Range | 200 V AC - 240 V AC |
| Country of Origin | Taiwan |
| Height | 1.7" |
| Width | 17.3" |
| Depth | 14.4" |
| Receptacle Type | IEC 60320 C13 |
| Environmentally Friendly | Yes |
| Network (RJ-45) | Yes |
| TAA Compliant | Yes |
| Mounting Orientation | Horizontal |
| Power Rating (Watt) | 2400 W |
| Receptacle Detail | 10 x IEC 60320 C13 |
| Plug/Connector Detail | 2 x IEC 60320 C14 |
| Environmental Compliance | Restriction of Hazardous Substances (RoHS) |
Marketing Information
- PDUMH15HVATNET 10-Outlet PDU
- 10 x C14 plug lock inserts
- 2 x C13 to C14 power cords, 3.6 m (11.8 ft.)
- SNMPWEBCARD configuration cable
- 2 x Mounting brackets, horizontal
- 2 x Mounting brackets, vertical
- 6 x Screws
- Owner's manual
Recommended for data centers, server rooms and network closets, this 1U switched power distribution unit enables redundant A/B power for network devices with single power cords. Dual 12-foot (3.7-meter) input cords with C14 plugs connect to separate primary and secondary mains circuits, backup generators, UPS systems or utility power grids. Plug-lock insert sleeves are included to prevent connected cords from becoming accidentally dislodged. The PDUMH15HVATNET constantly evaluates the power quality of both input sources and maintains continuous power to all outlets as derived from the primary source.
Switches from Primary to Secondary Power Source in Milliseconds
Dynamic solid-state automatic transfer switching (ATS) allows the IEC C13 PDU to switch to the secondary source within 2-5 milliseconds, should the primary source fail or become unstable, to ensure your connected equipment operates without interruption. An on-board ATS processor prevents switching if the secondary source is unavailable or of lower quality than the primary source.
Switched C13 Outlets Are Individually Controllable for Remote Reboots and Load Shedding
This switched power distribution unit distributes, monitors and manages selectable 200-240V power to equipment in network applications requiring individual outlet control, load shedding and remote monitoring of critical network components. Eight switched C13 outlets (two additional C13 outlets are unswitched) are subject to advanced network control and remote power monitoring, including the ability to turn on, turn off, reboot or lock out power to each outlet. Reducing the frequency of on-site visits can save you money and reduce downtime, thus lowering the PDU's total cost of ownership.
Check Essential Functions at a Glance
A front-panel digital load meter displays total PDU output current in amps. LEDs indicate on/off status of individual outlets and power status of primary and secondary inputs. An input-voltage select switch lets you toggle between high (220, 230 or 240V) or low (200 or 208V) voltage.
Built-In LX Platform Interface Gives You Unrestricted Remote Access to Your Equipment 24/7
The Java-free HTML5-based LX Platform network interface enables full remote access for PDU status monitoring and email notifications via secure web browser, SNMP, telnet or SSH. It supports 10/100 Mbps auto-sensing for optimum communication with an Ethernet network. Optional EnviroSense2 modules (sold separately) provide a variety of environmental monitoring capabilities. Protocols supported include IPv4, IPv6, HTTP, HTTPS, SMTP, SNMPv1, SNMPv2, SNMPv3, telnet, SSH, FTP, DHCP and NTP.
Reduce Service Calls with Auto Probe Autonomous Device Management
The Auto Probe feature (Firmware 15.5.2 and greater) checks the connectivity status of any networked device and automatically takes one or more user-configured actions if the device fails to respond; actions include outlet reboot, set SNMP traps, SNMP OID sets, and even script execution when used in conjunction with the Tripp Lite PowerAlert Network Shutdown Agent (PANSA).
Easy to Install Horizontally in an EIA-Standard 19 in. Rack
This ATS PDU mounts in 1U of space in 19-inch rack or rack cabinet using the included brackets and hardware.
TAA-Compliant for GSA Schedule Purchases
The PDUMH15HVATNET is compliant with the Federal Trade Agreements Act (TAA), which makes it eligible for GSA (General Services Administration) Schedule and other federal procurement contracts.
<a id="gfk-spex-minisite" rel="nofollow" href="javascript:void(0)" onclick="javascript:window.open('//content.etilize.com/mini-site/en_us/1036679989.html','_b
- HTTP
- HTTPSPowerAlert
- SMTP
- SNMPv1
- SNMPv2
- SNMPv3
- Telnet
- SSH
- FTP
- DHCP
- BOOTP and NTP protocols
Shipping & Dimensions
Similar Products
MANAGED RACK PDU, 2U, 3PH, L21-30P INPUT, 15FT CORD, 120/208V, 24A, OUTLETS: (24
EMAU19-15
COMPUTER POWER CORD, 360 ROTATING RIGHT ANGLED NEMA 5-15P TO C13 - HEAVY-DUTY, 1
P007-010-15RR
EATON END-OF-ROW DOOR SIDE-PANEL EXTENSION FOR RAPIDPOD AISLE CONTAINMENT SYSTEM
NXEORP969
EATON END-OF-ROW DOOR SIDE-PANEL EXTENSION FOR RAPIDPOD AISLE CONTAINMENT SYSTEM
NXEORP9630
EATON END-OF-ROW DOOR SIDE-PANEL EXTENSION FOR RAPIDPOD AISLE CONTAINMENT SYSTEM
NXEORP9627
EATON END-OF-ROW DOOR SIDE-PANEL EXTENSION FOR RAPIDPOD AISLE CONTAINMENT SYSTEM
NXEORP9624